ATS/ABCF Control

ABCF tm (Automatic Battery Capacity Failure)

Patent Registered Nr: P-00200700522

 

Goals

The Solution to Efficient Generator Fuel Consumption, maintain & monitor battery health

 

The Advantage

The advantages of ABCF are as follows:

  1. To efficient diesel generator fuel consumption for the Site or BTS which has poor quality Mains/PLN supply.
  2. To utilize battery health, maintain, and monitor battery condition.

The definitions of poor quality Mains/PLN are as follows:

  1. No Mains/PLN
  2. Frequent ON and OFF in short time period of time (10 minutes up to 2 hours) up to 5 times/day
  3. Frequent ON and OFF in long time period of time (2 hours up to 12 hours) up to 2 times/day.
  4. Voltage Ph-N <154 VAC or Ph-Ph <266 VAC (Indonesia Electricity Voltage System Only)
  5. 1 phase or 2 phase loss.

How it works

The starting sequence of generator does not depend on Mains fail, 1 or 2 phase loss, or Mains under voltage, but depends on Battery capacity condition and rectifier charging condition.

Start and Stop conditions:

  1. If  Mains/PLN OFF and the battery capacity is still in upper level, then the generator not start, but if battery capacity is under level then the generator will start. The level values are based on 'How full the battery is (in AH)' and battery level voltage.
  2. If Mains/PLN voltage drop in certain value but rectifier is still able to charge and supply load, then the generator not start.

 The Case

  • Most of Generator control will start Generator at three conditions:
    • Three Phase loss or Mains voltage = 0 VAC
    • One or Two Phase Loss
    • Mains Voltage drop below 70% of Nominal Value. Example: if voltage drop <154 VAC (70% x 220VAC), then controller will start Generator.
  • If such above conditions occurs in BTS, and operators using standard ATS/AMF, the Generator will start directly after the Mains/PLN phase loss or Voltage drop to 70% of nominal value. If the ATS/AMF Standard deployed in such condition, the generator will run everyday and need a lot of fuel consumption.
  • If using ABCF, the generator not directly start if Mains Phase loss, but wait until battery capacity down to certain value. Even in worst case the controller will not start generator when the Mains voltage down to 90 VAC where the rectifier is still able to charge battery and supply to load.

Value Added

  1. If NO Mains/PLN, the ABCF will automatically work as Charge/Discharge system mode.
  2. No need additional cost to equip BTS with battery monitoring system, ABCF provides it.
  3. Serial port RS232 ready for remote monitoring.
  4. Alarm dry contact ready for: System fail, Mains Fail, Generator Fail, Generator Run, Battery conditions 'Health' or 'Not Health'.
  5. Less labor cost to maintain generator.

 

 

General Specifications

 

Genset Controller, Brand Lovato type RGK60

Controller features:

Under and Over Voltage, Under and Over Frequency

Excessive Voltage Hysterisis , Unbalance Voltage

Low oil pressure, High engine temperature

Operating temperature: 0 - 70 oC

 

Measurements:

Voltage (p-p,p-n) Mains and Generator, Current Mains and Generator

Power (active, reactive and apparent), Frequency (45..65 Hz)

Energy (active and reactive), Power Factor

 

Controller Special Features:

Generator protection (overload and short circuit), 12 digital inputs all programmable

Maintenance interval setting

Safety copy of parameters in flash memory

 

Automatic Transfer Switch (ATS):

Brand Takada or Kyoritsu

No operating voltage required after change over (Mechanical latch mechanism)

High speed change over (13 ms)

Switching durability (Mechanical=50,000 times & Electrical=250,000 times)

Manual and automatic operation

 

Battery Monitor and Control:

System DC Voltage: 12, 24, 32, 36 and 48V in one controller

EPROM Data storage (No Loss data when power off or LVD Disconnect)

Output Contact:

- Genset ON/OFF based on SOC

- Genset ON/OFF based on Battery Volatage drop

- Alarm system fail and battery fail condition

Built-in 30 days data-logger

RS232 interface (optional)

Battery capacity monitoring: up to 20,000 ah

Operation temperature: 0 - 70 oC

 

 

ATS/ABCF Diagram

 